Assembly instructions for specialist personnel
Important information before
installation

For installation of the entire
system, the instructions in the
operating manuals for the in-
door and outdoor units must be
followed.

Bring the unit as close as pos-
sible to its installation location
in its original packaging. This
prevents any transport damage.

Check that the content of the
packaging is complete and
inspect the unit for visible trans-
port damage.
Report any defects immediately
to your contractual partner and
the carrier.

Lift the unit at the corners and
not at the refrigerant or con-
densation connections.

The refrigerant pipes (injec-
tion and suction pipe), valves
and the connections must be
insulated to seal them against
vapour diffusion. If necessary,
the condensation pipe should
also be insulated.

Choose an installation location
that ensures a free air inlet and
outlet. (See “Minimum clear-
ances” section.)

Do not install the unit in the im-
mediate vicinity of equipment
that radiates a large amount of
heat.
Installation close to heat radia-
tion reduces the performance of
the unit.

Do not open the blocking
valves for the refrigerant pipes
until the entire installation proc-
ess is complete.

Seal open refrigerant pipes
against the ingress of moisture
using appropriate caps or ad-
hesive tapes and never kink or
crimp the refrigerant pipes.
 Avoid unnecessary bends.
This
minimises the pressure loss
in the refrigerant pipes and
ensures a free return flow of
compressor oil.

In particular, you should take
precautions to ensure the oil
return if the outdoor unit is po-
sitioned above the indoor unit.
(See “Oil return measures”
section.)

If the basic length of the refrig-
erant pipe exceeds 5 metres,
refrigerant should be added.
For the quantity of additional
refrigerant, refer to the “Add-
ing refrigerant” section.

Use exclusively the refriger-
ant pipe screw caps supplied
and do not remove them until
shortly before connection to the
refrigerant pipes.

Set up all electrical connections
in line with the applicable DIN
and VDE regulations.

Always secure electrical lines
properly in the electrical termi-
nals.
Otherwise, fire could be
caused.
Wall feed throughs

A wall feed through of at least
70 mm in diameter and with
a 10 mm gradient from inside
to outside must be created for
each indoor unit.

We recommend that the hole is
padded out inside or lined, e.g.
with a PVC tube, to prevent
damage to the pipes.

When installation is complete,
the wall feed through must be
sealed with an appropriate seal-
ing compound.
Do not use materials containing
cement or lime.
Installation materials
The outdoor unit is either secured
to the wall using 4 screws and a
wall bracket or attached to the
floor using a base bracket.
Pipes in wall lead through
Control line
Condensation pipe
Injection pipe
Suction pipe
PVC pipe
REMKO RKS
8