Assembly instructions for specialist personnel
Important information before
installation
For installation of the entire
system, the instructions in the
operating manuals for the in-
door and outdoor units must be
followed.
Bring the unit as close as pos-
sible to its installation location
in its original packaging. This
prevents any transport damage.
Check that the content of the
packaging is complete and
inspect the unit for visible trans-
port damage.
Report any defects immediately
to your contractual partner and
the carrier.
Lift the unit at the corners and
not at the refrigerant or con-
densation connections.
The refrigerant pipes (injec-
tion and suction pipe), valves
and the connections must be
insulated to seal them against
vapour diffusion. If necessary,
the condensation pipe should
also be insulated.
Choose an installation location
that ensures a free air inlet and
outlet. (See “Minimum clear-
ances” section.)
Do not install the unit in the im-
mediate vicinity of equipment
that radiates a large amount of
heat.
Installation close to heat radia-
tion reduces the performance of
the unit.
Do not open the blocking
valves for the refrigerant pipes
until the entire installation proc-
ess is complete.
Seal open refrigerant pipes
against the ingress of moisture
using appropriate caps or ad-
hesive tapes and never kink or
crimp the refrigerant pipes.
Avoid unnecessary bends.
This
minimises the pressure loss
in the refrigerant pipes and
ensures a free return flow of
compressor oil.
In particular, you should take
precautions to ensure the oil
return if the outdoor unit is po-
sitioned above the indoor unit.
(See “Oil return measures”
section.)
If the basic length of the refrig-
erant pipe exceeds 5 metres,
refrigerant should be added.
For the quantity of additional
refrigerant, refer to the “Add-
ing refrigerant” section.
Use exclusively the refriger-
ant pipe screw caps supplied
and do not remove them until
shortly before connection to the
refrigerant pipes.
Set up all electrical connections
in line with the applicable DIN
and VDE regulations.
Always secure electrical lines
properly in the electrical termi-
nals.
Otherwise, fire could be
caused.
Wall feed throughs
A wall feed through of at least
70 mm in diameter and with
a 10 mm gradient from inside
to outside must be created for
each indoor unit.
We recommend that the hole is
padded out inside or lined, e.g.
with a PVC tube, to prevent
damage to the pipes.
When installation is complete,
the wall feed through must be
sealed with an appropriate seal-
ing compound.
Do not use materials containing
cement or lime.
Installation materials
The outdoor unit is either secured
to the wall using 4 screws and a
wall bracket or attached to the
floor using a base bracket.
Pipes in wall lead through
Control line
Condensation pipe
Injection pipe
Suction pipe
PVC pipe