Edition GB – S08REMKO RKSRKS 435H, RKS 448HCombination indoor unitsOperation · Technology · Spare parts
Ensure a continuous, unim-peded air supply from outside, if possible through opposite air openings of sufficient size.Comply with any static and ot
10. Check that the border has the correct shape (Figure 3). 11. First connect the refrigerant pipes to the blocking valves by hand to ensure a correct
Condensation connectionBecause the temperature on the register is below the dew point, condensation is formed during heating. The lower housing cover
R(M,V)S(X)32N(1)C(U)M1M2BLBLBNBNYEYEYERDRDRDBKNBLElectrical connection diagramWith this unit combination, a compressor contact is fitted in the factory
R(M,V)S(X)2N(1)C(U)M1M2BLBLBNBNYEYEYERDRDRDBKNBLFCNLVBLBLBKR(M,V)S(X)32N(1)C(U)M121R(M,V)S(X)C(U)M2BLBLBLBNBNBNYEYEYERDRDRDBKRKS 435H combined with RX
After successfully completing the leak test, the vacuum pump should be connected to the valve connec-tions on the outdoor unit through the manometer s
Test run1. Remove the covers from theRemove the covers from the valves.2. Start initial operation by brieflyStart initial operation by briefly opening
Technical data17REMKO RKSSeries RKS 435H RKS 448HFunctions Outdoor unit for cooling and heatingRated refrigerating capacity 1)ing capacity 1) kW 3,49
Unit illustration1234678 91110Dimensions and design subject to modifications in the course of technical development.12135REMKO RKS18
Spare parts listFor spare parts orders, always specify the IT no., the unit no. and the unit type (see rating plate)!No. Designation RKS 435H RKS 448H
Subject to technical modifications, no liability accepted for specifications in this document!REMKO ACROSS EUROPE… and in your area!Rely on our experien
ContentMade by REMKOThis operating manual must be read carefully before initial operation / using the equipmentThis manual is part of the unit and mu
Safety instructionsRead the operating manual thoroughly before initial opera-tion of the unit. It contains useful It contains usefulIt contains usefu
Refrigerating circuit RKS…H diagramThe units are supplied in robust transport packaging. Immediately ImmediatelyImmediately after delivery, check the
OperationThe outdoor unit is operated by the controller for the connected indoor unit.For this reason, the instructions in the “Operation” section of
Fault Possible cause Check RemedyThe unit is not running or shuts itself down.Power failure. Is all electrical equipmentworking?Check voltage andwait
Assembly instructions for specialist personnelImportant information before installationFor installation of the entire system, the instructions in th
Choosing the installation locationThe outdoor unit is designed for horizontal upright installation outdoors. The installation location for the unit