Test run
1. Remove the covers from theRemove the covers from the
valves.
2. Start initial operation by brieflyStart initial operation by briefly
opening the blocking valves
on the outdoor unit until the
manometer indicates a pressure
of approx. 4 bar.
3. Check all connections for leaksCheck all connections for leaks
using leak detection spray or
appropriate equipment.
4. If you have identified any leaks,If you have identified any leaks,
open the blocking valves by
turning them as far as possible
anticlockwise using a hexagonal
wrench.
If leaks are identified, the
defective connection should be
replaced. It is then essential to It is then essential toIt is then essential to
repeat vacuum generation and
drying.
5. Turn on the on-site masterTurn on the on-site master
switch or fuse.
6. Set the target temperature onSet the target temperature on
the indoor unit to a lower tem-
perature than the current room
temperature using the remote
control.
7. Switch the indoor unit to cool-Switch the indoor unit to cool-
ing mode.
9. Check the control of the indoorCheck the control of the indoor
unit using the functions de-
scribed in the operating manu-
al:
timer, temperature settings and
all mode settings.
10.
Measure overheating, the
external, internal, outlet and
evaporation temperatures and
enter the measured data in the
initial operation log.
11.
Remove the manometer and
re-attach all parts previously
removed.
Make sure that the seals are
fitted in the covers.
Final measures
Re-fit all parts removed.
Instruct the operator in how to
use the system.
8. During the test run, check theDuring the test run, check the
function and correct setting
of all regulating, control and
safety devices.
Dimensions and design subject to modifications in the course of technical development.
Unit dimensions
Because of the start-delay, the
compressor starts running a
few minutes later.
NOTE
540120
850
285
540
RKS 435H / RKS 448H
All figures in mm
290
770
REMKO RKS
16
Vista de página 15
1 2 ... 11 12 13 14 15 16 17 18 19 20

Comentários a estes Manuais

Sem comentários